EATON PW5115 RM 1500 - Uninterruptible Power Supply
|

 Click to zoom
EATON PW5115 RM 1500 - Uninterruptible Power Supply
The Powerware 5115 Rackmount UPS is the ideal high-density power protection solution ideal for servers, storage systems, network equipment and other critical devices. The slim design and wide range of installation possibilities make the Powerware 5115 Rackmount the most versatile UPS available. Occupying only 1U of rack height, the 5115 conserves valuable rack space for other critical devices while delivering powerful performance. Features: - Unique chassis design adapts to rackmount, wall mount, side cabinet (zero U), and bench top applications
- ABM® Technology significantly extends battery service life
- True sine wave output delivers smooth, continuous power
- Buck and Boost Automatic Voltage Regulation corrects incoming voltage fluctuations
- Load segments enable scheduled shutdowns and extend backup time for critical devices
- Hot-swappable batteries minimize downtime, simplify service and extend service life of UPS
- Standard USB and RS232 serial ports extend communication capacity
- X-SlotTM card communication options extend power management capability
- Power management software (included) ensures data integrity
- Provides investment protection with a two-year limited warranty, 10-year pro-rated warranty, $150,000 load protection guarantee (U.S. and Canada)
 |
 Specifications
Electrical Input Nominal voltage | 120V models are 110V or 120V user-selec table; 230V models are 220V, 230V or 240V user-selectable | Input voltage ranges | +- 20% for nominal voltage at full load for user-selectable voltages | Operating frequency | 50/60Hz, Auto-sensing | Frequency range | 46-65Hz |
Electrical Output On utility voltage regulation | -10% to +6% of nominal | On battery voltage regulation | ±5% RMS | Voltage wave shape (on battery) | Sine wave | Output protection | Electronic current limit |
Communications User interface | LED status display with AC power on, load Group, Overload, On Battery and General Alarm indicators, Site Wiring Fault Indicator on rear panel for low volt models. | Audible alarms | For various UPS alarm conditions, including: On Battery, Low Battery, Overload, UPS fault | Network transient protector | UL 497 A, In/out jacks RJ45 (high voltage models network protection) & RJ11 (low voltage models modem protection) | X-Slot | optional ConnectUPS-X Web/SNMP/xHub Card; | Communication cards | USB card ; X-Slot Relay card | Standard communications | 1 x RS-232 Serial Port & 1 x USB Port | Cable | 6-foot communications cable included | Power Management Software | Powerware Software Suite CD-ROM (bundled with UPS) |
Battery Battery type | Sealed, lead-acid; maintenance free | Battery run time | See Battery Run Time chart | Battery replacement | Hot-swappable internal batteries | Recharge time | <3 hours to 90% usable capacity | Start-on-battery | Allows start of UPS without utility input |
General Diagnostics | Self-test @ power up | Transfer time | 2-4 ms typical | Dimensions and weights | See Model Selection Guide | Overload (normal operation) | 110% overload, shutdown after 3 minutes. 150% overload, shut down 10 cycles |
Environmental Safety markings | 120V Models UL; cUL; | | 230V Models C-Tick; CE, TUV, cUL, UL | Safety conformance | 120V Models: UL 1778; UL497A; cUL (CAN/CSA C22.2, No. 107.1) 230V Models: UL1778, UL 497A (data line only); cUL (CAN/CSA C22.2, No. 107.1); EN 50091-1-1 and IEC 60950 | EMC compliance | 120V Models: FCC Part 15 subpart J Class A, ICES-003; 230V Models: EN 50091-2. FCC Part 15 subpart J Class A , ICES-003 | Operating temperature | 0 to 40º C (32 to 104º F) | Storage temperature | -15 to 50º C (5 to 122º F) | Relative humidity | 5% to 95% non-condensing | Surge suppression | ANSI C62.41 Category A (formerly IEEE 587) | Audible noise | Less than 40 dBA typical | Altitude | Up to 3000M (10,000 ft) without derating |
|
|
|
|